Note: Production discontinued. The product is replaced by the Unipi Patron L207.
Unipi Axon L205 is a programmable logic controller designed for automation, control, regulation and monitoring. The L205 features a high number of digital and relay I/Os complemented by a single analog I/O and three serial interfaces (RS485 + RS232). With a total number of 70 I/Os, the L205 offers the highest number of inputs/outputs of all Axon controllers. The controller is also provided with a 1-Wire interface for connection of digital temperature or humidity sensors.
Features
Unipi Axon L205 is a programmable logic controller designed for automation, control, regulation and monitoring. The L205 features a high number of digital and relay I/Os complemented by a single analog I/O and three serial interfaces (RS485 + RS232). With a total number of 70 I/Os, the L205 offers the highest number of inputs/outputs of all Axon controllers. The controller is also provided with a 1-Wire interface for connection of digital temperature or humidity sensors.
Digital inputs | 36 | Common features 1.2GHz quad-core ARM CPU, 1GB RAM 8GB eMMC onboard memory 2× USB 2.0 1× 1Gbit Ethernet Wi-Fi, Bluetooth Extended operating temperature range Aluminium chassis (IP20) |
Digital outputs | 4 | |
Relay outputs | 28 | |
Analogue inputs | 1 | |
Analogue outputs | 1 | |
RS485 serial interface | 2 | |
RS232 serial interface | 1 | |
1-Wire bus | 1 | |
Ethernet | 1 |
Digital inputs (DI) are designed for reading states of two-state devices such as various digital sensors, switches and buttons, motion sensors etc. All digital inputs feature counter functionality by default.
Digital outputs (DO) are applicable for switching two-state devices using direct current (DC) such as locks, external relays, contactors etc. DO’s can be also used for analog control thanks to the pulse-width modulation (PWM) function.
Relay outputs (RO) serve for switching devices with higher current draw and devices requiring alternating current (AC) such as water heaters, pumps, contactors or external relays with higher switching current.
Analog input (AI) is designed to measure voltage or current in order to read values from various analog sensors (pressure meters, tension gauges etc.).
Analog output (AO) is used to control and regulate devices such as three-way valves, electric motors, inverter drives, heat exchangers etc. by direct current or voltage.
Axon controllers are powered by a quad-core, 1.2GHz Alwinner H5 CPU and feature a 1GB RAM for an excellent performance. The 8GB onboard eMMC memory then offers better reliability compared to systems relying on microSD cards as memory storage.
By default, all Axon controllers feature RS485 serial lines. This type of interface usually uses the Modbus RTU protocol and can be used for communication with various devices such as Extension xS extension modules, energy meters, touchscreen HMI displays, controllers from other vendors, various sensors etc. A single bus can support dozens of devices while its length can reach up to several hundred meters.
Selected models also feature a single RS232 serial line. In the field of automation, this interface is usually used for communication with various converters, closed-in technologies or display devices such as HMI panels.
A single 1-Wire bus is also available on selected models. This interface uses 2-3 conductors for collecting data from various 1-Wire sensors such as thermometers, humidity meters, light intensity sensors etc.). A single 1-Wire bus supports up to 15 devices, the overall length of the bus can reach up to 200 meters.
By default, all Axon controllers feature a single 1Gbit Ethernet port for network communication.
Thanks to the software openness of Unipi controllers customers can choose from a broad range of software solutions and are not limited to a single platform Among supported solutions are both commercial and open-source systems. Visit the Other software overview for the list of other supported solutions.
The main supported solution is the Mervis control system - a platform developed under the IEC 61131-3 standard for PLC programming, that includes SCADA interface for remote management and monitoring, a comprehensible development environment, a human-machine interface (HMI) editor and an online/on-premise database for storing historical data and retrospective analysis of the controlled technology's operation.
Aside from commercial platforms you can also choose any from the list of supported open-source solutions, or use the EVOK API (Websocket, REST,...) Modbus TCP, SysFS or other tools for implementing your logic in any programming language. Visit this link for the list of supported software solutions.
All components of the controller are encased within a durable aluminium chassis (IP20 protection). The controller is designed for mounting on a standard DIN rail (35 mm).
Model | DI | DO | RO | AI | AO | RS485 | RS232 | 1-Wire | Common features |
Type S, the size on DIN rail: 4 modules (7 cm) |
1.2GHz quad-core ARM CPU 1GB RAM, 8GB eMMC onboard memory 2× USB 2.0 Wi-Fi, Bluetooth Aluminium chassis (IP20) Extended operating temperature range |
||||||||
S105 | 4 | 4 | - | 1 | 1 | 2 | 1 | 1 | |
S115 | 4 | 4 | - | 1 | 1 | 4 | - | 1 | |
S1551 | 4 | 4 | - | 1 | 1 | 2 | 1 | 1 | |
S205 | 8 | - | 8 | - | - | 1 | - | 1 | |
S215 | 8 | - | 8 | - | - | 1 | 1 | - | |
S505 | - | - | - | 4 | 4 | 1 | - | 1 | |
S515 | - | - | - | 4 | 4 | 1 | 1 | - | |
Type M, the size on DIN rail: 8 modules (14 cm) | |||||||||
M205 | 20 | 4 | 14 | 1 | 1 | 2 | 1 | 1 | |
M2652 | 20 | 4 | 14 | 1 | 1 | 2 | - | 1 | |
M525 | 8 | 4 | 5 | 5 | 5 | 3 | 1 | 1 | |
M535 | 4 | - | 5 | 8 | 8 | 2 | 1 | - | |
M5652 | 8 | 4 | 5 | 5 | 5 | 3 | - | 1 | |
Type L, the size on DIN rail: 12 modules (21 cm) | |||||||||
L205 | 36 | 4 | 28 | 1 | 1 | 2 | 1 | 1 | |
L525 | 24 | 4 | 19 | 5 | 5 | 3 | 1 | 1 |
1- 2× Ethernet (1 Gbit + 10/100 Mbit)
2 - wireless LTE module
Instruction leaflet Technical and safety information |
download | |
Modbus register map Table overview of Modbus registers |
download | |
Certification Declaration of conformity |
download | |
Product datasheet Product features and technical information |
download |
Digital inputs | 36 |
Digital outputs | 4x |
Relay outputs | 28 |
Analog inputs | 1 |
Analog outputs | 1 |
CPU | 4x 1.2 GHz |
RAM | 1 GB |
RS232 interface | 1 |
RS485 interface | 2 |
Ethernet | 1 Gbit |
USB 2.0 | 2 |
1-Wire bus | Yes (galvanically isolated) |
Power | 24V DC |
Internal memory | 8GB eMMC |
Dimensions | 210 mm x 90 mm x 60 mm |
Mounting | DIN (35 mm) |
Weigth | 585 g |
RTC backup | max. 7 days |